12-Month UV Fouling Study on Unfiltered Source Water

机译:未经过滤的原水的12个月紫外线污染研究

获取原文
获取原文并翻译 | 示例

摘要

The Portland Water Bureau (PWB) undertook a study in 2009-2010 to investigate foulingrntendencies of its unfiltered source water with UV equipment. The 12-month study was conducted withrnthree different UV reactors; two medium pressure reactors and one low-pressure high-output (LPHO)rnreactor. Results showed that the un-wiped medium-pressure lamp sleeves demonstrated significantrnamounts of fouling during the fall. During the remainder of the year the un-wiped medium-pressure lamp sleeves showed little or no fouling. The un-wiped LPHO sleeves demonstrated no significant fouling during any month of the year. PWB was able to use the results of this study to aid in the pre-selection process of UV equipment for full-scale design.
机译:波特兰水务局(PWB)在2009-2010年进行了一项研究,以调查其未过滤的原水和紫外线设备的污染趋势。为期12个月的研究是在三个不同的紫外线反应器中进行的; 2个中压反应堆和1个低压高输出(LPHO)反应器。结果表明,未擦拭的中压灯套在秋天期间表现出明显的结垢现象。在一年的剩余时间内,未擦拭的中压灯套几乎没有积垢。未擦拭的LPHO袖套在一年中的任何月份均无明显污垢。 PWB能够利用这项研究的结果来协助UV设备的预选过程进行全面设计。