NDMA Formation from Gaskets Used In Water Storage Tanks

机译:NDMA由储水箱中使用的垫圈形成

获取原文
获取原文并翻译 | 示例

摘要

Elevated concentrations of N-nitrosodimethylamine (NDMA) were detected in arndistribution system during routine monitoring. The high concentrations were localized, and arntemporary storage tank was suspected to be the source of the problem. Samples of the gasketsrnused in the construction of the temporary tank were gathered and subjected to bench-scale tests.rnThese tests demonstrated that the gaskets, when exposed to system water, did produce NDMA asrnwell as other nitrosamines. Scaling up the surface-area-to-volume ratios from bench-scale tornfull-scale, the concentrations of NDMA measured in the bench-scale tests were not high enoughrnto account for all of the NDMA measured in the full-scale tank, assuming complete mixing.