首页> 外文会议>2012 international conference on future communication and computer technology >Fault Diagnosis Method for Transformer Bushing Based on RS Theory and Influence Factors Analysis
【24h】

Fault Diagnosis Method for Transformer Bushing Based on RS Theory and Influence Factors Analysis

机译:基于RS理论和影响因素分析的变压器套管故障诊断方法

获取原文
获取原文并翻译 | 示例

摘要

Based on the test results of dielectric loss factor (tan8) of transformer bushings in an artificial climate chamber, in this paper a Decision Table to analyzed the influence of tan5 is built which based on the Rough Set (RS) theory, and the effect of environment factors and voltage on the tan8 of capacitive equipment was analyzed by the Rough Set theory, and the results shows that the influence of temperature and humidity is much more than the voltage, which can be ignored. However, the old bushing is more influenced by the humidity factor compared to the new one. So, the fault of capacitive equipment can be diagnosed by RS theory and influence factors analysis.
机译:根据人工气候室内变压器套管的介电损耗因子(tan8)的测试结果,本文基于粗糙集(RS)理论,建立了一个决策表来分析tan5的影响,以及利用粗糙集理论分析了电容设备tan8的环境因素和电压,结果表明温度和湿度的影响远大于电压的影响,可以忽略不计。但是,旧套管比新套管受湿度因素的影响更大。因此,可以通过RS理论和影响因素分析来诊断电容设备的故障。