In oil-immersed transformers, static electrification phenomenon is caused by insulating oil flowing on solid insulator such as pressboard (PB). In Japan, as a countermeasure, 1, 2, 3-benzotriazol (BTA) is used to suppress static electrification. But, recent years, it has been reported that static electrification phenomenon increases with aging owing to oxidation of insulating oil, operation history of transformers with overhaul, and so on [1]. This paper deals with the verification of BTA effect on the increase of electrostatic charging tendency (ECT) due to aging, and evaluation for the influence of air exposure on static electrification during overhaul using the aging oil from 500 kV transformer by performing overhaul process according to actual operation and accelerated aging test.
机译:在油浸式变压器中,静电带电现象是由绝缘油在压板(PB)等固体绝缘体上流动引起的。在日本,作为对策,使用1,2,3-苯并三唑(BTA)来抑制静电。但是,近年来,据报道,由于绝缘油的氧化,大修变压器的运行历史等,静电起电现象会随着老化而增加[1]。本文根据500 kV变压器的老化油,根据BTA对老化引起的静电荷趋势(ECT)增加的影响进行验证,并评估空气暴露对检修期间使用500 kV变压器的老化油对空气静电的影响。实际操作和加速老化测试。