Fitting algorithm for power tower grounding resistance with vertical layered soil model

机译:垂直层状土模型对电力塔接地电阻的拟合算法

获取原文
获取原文并翻译 | 示例

摘要

The accurate algorithm, which is used in the calculation of tower grounding resistance of power line in vertical layered soil, is difficult for normal engineering personnel to handle. Based on Green function, the resistance of typical tower grounding device is calculated. Therefore, the fitting function, which represents the relationship between resistivity of vertical layered soil and resistance values of grounding device, is deduced with the hyperbolic function as a fitting function using the least squares curve fitting methods. At last, the fitting formula of tower grounding resistance with the vertical layered soil model is acquired. According to the precision analysis, it is found that the accuracy of proposed formula is related with the initial value, but its maximum error does not exceed 10%.
机译:用于垂直层状土壤中电力线铁塔接地电阻计算的精确算法对于普通工程人员来说很难处理。基于格林函数,计算出典型塔架接地装置的电阻。因此,利用双曲线函数作为拟合函数,使用最小二乘曲线拟合方法,推导了代表垂直层状土壤电阻率与接地装置电阻值之间关系的拟合函数。最后,得到了塔架接地电阻与竖向分层土体模型的拟合公式。根据精度分析,发现所提公式的精度与初始值有关,但最大误差不超过10%。