As the wind power penetration continues to increase, wind turbines are required to provide Low Voltage Ride-Through (LVRT) capability, thus new grid codes for wind turbines are established. Most grid codes provide the LVRT curve only for the connection to the transmission system. Only few of them include the distribution system and yet the measuring of the terminal voltage do not consider unbalanced operating conditions. This paper analyses the fulfillment of LVRT requirements under unbalanced voltage conditions for doubly-fed induction generator (DFIG) wind turbines connected to the distribution system. Three different terminal voltage measurement schemes are used and analyzed. The simulations are carried out in EMTP-RV software and the results indicate that for highly imbalanced systems all three phases must be independently analyzed.
机译:随着风力渗透率的不断提高,要求风力涡轮机提供低压穿越(LVRT)功能,因此建立了新的风力涡轮机电网规范。大多数电网代码仅提供LVRT曲线用于连接到传输系统。其中只有少数几个包括配电系统,但是端子电压的测量并未考虑不平衡的工作条件。本文分析了与配电系统连接的双馈感应发电机(DFIG)风力发电机在不平衡电压条件下LVRT要求的实现情况。使用和分析了三种不同的端子电压测量方案。仿真是在EMTP-RV软件中进行的,结果表明,对于高度不平衡的系统,必须独立分析所有三相。