In order to interconnect the power systems of Uruguay and Brazil with different frequencies, a new 500 MW HVDC back-to-back (HVDC BtB) frequency converter station was built. A complete model of this HVDC BtB has been developed by the authors with ATP (Alternative Transients Program) for conducting power system electromagnetic transient (EMT) simulations. In relation to the work carried out, this paper presents the following issues: the main technical characteristics of the HVDC BtB, the Static Characteristic under normal and abnormal operating conditions and control loops associated, bridge converter and thyristor firing scheme modelling, power converter transformers modelling, temporary over/under voltage control, initialization of the back-to-back model, application and removal of balanced three-phase fault at both rectifier and inverter sides, single phase fault with successful auto-reclosure at Uruguay side. In order to evaluate the ATP model the simulation results were compared against PSCAD and RTDS results given by the manufacturer.
机译:为了将不同频率的乌拉圭和巴西的电力系统互连,建立了一个新的500 MW HVDC背靠背(HVDC BtB)变频器站。作者已经利用ATP(交流暂态程序)开发了此HVDC BtB的完整模型,用于进行电力系统电磁暂态(EMT)模拟。关于所进行的工作,本文提出了以下问题:HVDC BtB的主要技术特性,正常和异常运行条件下的静态特性以及相关的控制回路,桥式转换器和晶闸管点火方案建模,功率转换器变压器建模,暂时的过压/欠压控制,背对背模型的初始化,整流器和逆变器侧的平衡三相故障的应用和消除,乌拉圭侧的成功自动重合闸的单相故障。为了评估ATP模型,将仿真结果与制造商提供的PSCAD和RTDS结果进行了比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号