摘要

For the first time as East Japan Railway Company, we adopted the thyristor changeover switch in the changeover section of Shin-Yono sectioning post. However, Shin-Yono SP has a characteristic that the stray capacitance of the neutral section is large. Therefore, if a 'partial turn-off' phenomenon occurs in the thyristor constituting the changeover switch, in the worst case, it may lead to failure of the equipment. In this paper, we analyzed the conditions under which partial turn-off occurs, focusing on the voltage phase displacement. We also examined the settling and sequence of asynchronous detection relays introduced as a countermeasure.
机译:作为东日本铁路公司,我们首次在新与野切片路段的转换段中采用了晶闸管转换开关。然而,Shin-Yono SP具有中性部分的杂散电容大的特性。因此,如果在构成转换开关的晶闸管中发生“部分关断”现象,则在最坏的情况下可能导致设备故障。在本文中,我们分析了部分关断发生的条件,重点是电压相移。我们还检查了作为对策引入的异步检测继电器的建立和顺序。