A Method for On-Going Commissioning of VRV Package Systems Using a Simulation Model

机译:一种使用仿真模型进行VRV包装系统持续调试的方法

获取原文
获取原文并翻译 | 示例

摘要

Variable refrigerant volume (VRV) systems, which have several indoor units and a single outdoor unit, have become very popular HVAC systems in Japan. However, some systems may be operated under inefficient conditions and consume excessive energy, since verification of system performance is not conducted. Although the performance of systems should be evaluated by some indices such as coefficient of performance (COP), calculating such a value is difficult, because the heat load handled by machines is not known. A simulation model based on a refrigeration cycle was proposed to evaluate system performance. Basic conditions for evaporation and condensation were defined from conditions provided in Japanese Industrial Standards (JIS). Flow rate of refrigerant was calculated from heat load under full occupancy and enthalpy difference of the evaporator. If power consumption exceeds the calculated value, malfunctions or inadequate conditions are considered to occur. The method presented here can be used for on-going commissioning of VRV package systems.
机译:具有多个室内单元和一个室外单元的可变制冷剂量(VRV)系统已成为日本非常流行的HVAC系统。但是,由于未对系统性能进行验证,因此某些系统可能会在低效条件下运行并消耗过多的能量。尽管应该通过诸如性能系数(COP)之类的一些指标来评估系统的性能,但是由于不知道由机器处理的热负荷,因此很难计算该值。提出了一种基于制冷循环的仿真模型来评估系统性能。蒸发和冷凝的基本条件由日本工业标准(JIS)提供的条件定义。制冷剂的流量由蒸发器的满载和焓差下的热负荷计算得出。如果功耗超过计算值,则认为发生故障或条件不足。此处介绍的方法可用于VRV包装系统的持续调试。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号