The paper deals with problems of combinations of wind and thermal actions of climatic origin on the level of two-dimensional random variable (V,T) where random variables V and T of values v and T denote respectively the ten-minutes mean wind velocity and the 24-hours mean ambient air temperature. Examples of various experimentally determined probability density functions f(v, τ) are given and a way of precise determination of coincidence coefficients of the analyzed actions is proposed; this may be useful in standardization of this problem. Moreover, problems of description of 24-hours transient temperatures in summer and winter are also presented. In the second part of the paper, the results of static-strength calculations of 150 m - high cooling tower for several different possible combinations of wind w and thermal τ actions and dead load g are considered and analyzed.
机译:本文在二维随机变量(V,T)的水平上处理了气候和风的热源组合的问题,其中随机变量V和T的值v和T分别表示十分钟的平均风速和24小时平均环境温度。给出了各种实验确定的概率密度函数f(v,τ)的示例,并提出了一种精确确定所分析动作的重合系数的方法。这对于此问题的标准化可能很有用。此外,还提出了描述夏季和冬季的24小时瞬态温度的问题。在本文的第二部分中,考虑并分析了150 m高冷却塔的静强度计算结果,该塔针对风w和热τ作用以及静载g的几种不同可能组合。