The transformer's operating temperature has a direct effect on its power transfer capability, insulation aging and losses. Utilities try to maintain their transformer coolers within acceptable working condition bounds in order to keep this operating temperature within manufacturers design limits. A study is being conducted in order to assess the influence of different ambient, meteorological and operating factors on the performance of transformer coolers. For this purpose two transformers on the Niagara Mohawk system have been instrumented with sensors that monitor oil and air temperatures, oil and air flow rates, ambient conditions and transformer loading under operating conditions. This paper presents preliminary results of the study of the effect of fouling on large power transformer temperatures. This is established by comparing measured top oil temperature vs. computed temperature over time. The study demonstrates that cooler fouling does have an effect on the top oil temperature.
机译:变压器的工作温度直接影响其动力传递能力,绝缘老化和损耗。实用程序尝试在可接受的工作条件范围内维护变压器冷却器,以便在制造商设计限制范围内保持此操作温度。正在进行一项研究,以评估不同环境,气象和操作因素对变压器冷却器性能的影响。为此目的,尼亚加拉莫霍克系统上的两个变压器已经用传感器仪表,在操作条件下监测油和空气温度,油气和空气流量,环境条件和变压器负载。本文介绍了污染对大型电力变压器温度的影响研究的初步结果。这是通过比较测量的顶部油温与计算温度随时间的测量值来建立。该研究表明,冷却器污垢确实对顶部油温产生了影响。