首页> 外文会议>10th IET International Conference on Developments in Power System Protection : Managing the Change >Static characteristics analysis of ground MHO distance relay for UHV lines
【24h】

Static characteristics analysis of ground MHO distance relay for UHV lines

机译:特高压线路地面MHO距离继电器的静态特性分析

获取原文

摘要

UHV/EHV long transmission lines have large distributed capacitance and shunt reactors, which may have significant effects on the operation of a traditional distance relay. The distance relay without considering any of the above two factors will operate with serious overreaching or underreaching. Several papers have analysed these effects on the measuring impedance of distance relay and proposes different schemes to ensure the reliability and selectivity of distance relay for UHV/EHV long transmission lines. This paper compares the static characteristics of these schemes, and proposes a hybrid scheme which is easier to calculate and set.
机译:UHV / EHV长输电线具有较大的分布电容和并联电抗器,可能会对传统距离继电器的运行产生重大影响。不考虑以上两个因素中的任何一个的距离继电器将在严重超范围或不足范围内工作。几篇论文分析了这些对距离继电器的测量阻抗的影响,并提出了不同的方案来确保特高压/超高压长距离线路的距离继电器的可靠性和选择性。本文比较了这些方案的静态特性,并提出了一种易于计算和设置的混合方案。