首页> 外文会议>Annual IEEE Applied Power Electronics Conference and Exposition >Fast voltage detection method for the voltage ride through operation of grid-tied renewable energy generation systems
【24h】

Fast voltage detection method for the voltage ride through operation of grid-tied renewable energy generation systems

机译:用于并网可再生能源发电系统运行的快速电压检测方法

获取原文

摘要

As the scale of renewable energy resources connected to the grid is increasing remarkably, the strict gird codes are formulated in order to ensure the grid safety. Among the grid codes, the low voltage ride through (LVRT) regulation is important because it defines the acquired response to support the grid stability. This paper proposed a new voltage detection method, which consists of the traditional three-phase phase lock loop and a new low voltage detection procedure for the low voltage ride through operation of grid-tied renewable energy generation systems. This method can detect the amplitude of voltage sag within 5ms by tracking either the maximum point or the zero point. Finally, validity and accuracy of the proposed method is verified by simulation and experimental results.
机译:随着连接到电网的可再生能源的规模显着增加,制定了严格的电网规程以确保电网安全。在电网规范中,低电压穿越(LVRT)调节很重要,因为它定义了获得的响应以支持电网稳定性。本文提出了一种新的电压检测方法,该方法包括传统的三相锁相环和用于并网可再生能源发电系统的低压穿越的低压检测程序。通过跟踪最大点或零点,该方法可以在5ms内检测电压骤降的幅度。最后,通过仿真和实验结果验证了该方法的有效性和准确性。