首页> 外文会议>International Conference on Lightning Protection >Application of an analysis technique to characterise impulse response of grounding systems
【24h】

Application of an analysis technique to characterise impulse response of grounding systems

机译:分析技术在诱导接地系统表征脉冲响应的应用

获取原文

摘要

Transient response plays a key role in the evaluation of the performance of grounding systems and for the protection of electrical installations under lightning strikes. The frequency spectrum of the lightning impulse contains harmonics components up to the megahertz range. The measured transient response of grounding systems under test may be distorted by spurious high frequency interference in the acquired signals, which presents challenges for the accurate analysis of high frequency performance of such systems. In this paper, the high frequency performance of a rod electrode is investigated based on measurements of its transient response under impulse energisation. A practical method is implemented to eliminate the high frequency noise in the measured voltage and current shapes, which allows a frequency domain analysis based Fast Fourier Transforms.
机译:瞬态响应在评估接地系统的性能和保护闪电下的电气装置中起着关键作用。闪电脉冲的频谱包含距离Megahertz范围的谐波组件。所测试的接地系统的测量瞬态响应可以通过所获取的信号中的虚假高频干扰来扭曲,这呈现了对这种系统的高频性能进行准确分析的挑战。在本文中,研究了基于脉冲通电下的瞬态响应的测量来研究杆电极的高频性能。实现了实际方法以消除测量电压和电流形状中的高频噪声,这允许基于频域分析的快速傅里叶变换。