首页> 外文会议>International Conference on Ecological Vehicles and Renewable Energies >Stability of battery energy storage system operating with diesel generator in a stand-alone microgrid
【24h】

Stability of battery energy storage system operating with diesel generator in a stand-alone microgrid

机译:在独立微电网中使用柴油发电机运行的电池储能系统的稳定性

获取原文

摘要

In this paper, current control for ensuring a stability of battery energy storage system (BESS) is analyzed in a stand-alone microgrid which includes 50kW BESS and 50kW diesel generator. BESS with LCL filter is charged from the diesel generator when state of charge of battery bank is insufficient, and the current control of BESS may become unstable since a large synchronous inductance of diesel generator may generate a LCL filter resonance. No damping, Passive damping and active damping are applied to the current control so as to damp out a filter resonance and improve stability. Influence of the synchronous inductance is analyzed in the frequency domain and discrete time domain. The stable current control is guaranteed, and current waveforms are improved regardless of the significant synchronous inductance of diesel generator.
机译:在本文中,在包括50kW BESS和50kW柴油发电机的独立微电网中分析了用于确保电池储能系统(BESS)稳定性的电流控制。当电池组的充电状态不足时,带有LCL滤波器的BESS由柴油发电机充电,并且由于柴油发电机的大的同步电感可能会产生LCL滤波器谐振,因此BESS的电流控制可能会变得不稳定。在电流控制中不采用阻尼,被动阻尼和主动阻尼,以消除滤波器谐振并提高稳定性。在频域和离散时域中分析了同步电感的影响。保证了稳定的电流控制,并且改善了电流波形,而与柴油发电机的显着同步电感无关。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号