首页> 外文会议>International Conference on Industrial Technology and Management >Improving Airflow and Thermal Distribution in a Real Data Centre Room Through Computational Fluid Dynamics Modeling
【24h】

Improving Airflow and Thermal Distribution in a Real Data Centre Room Through Computational Fluid Dynamics Modeling

机译:通过计算流体动力学建模改善实际数据中心机房中的气流和热分布

获取原文

摘要

A Data Centre is a physical space that groups together computer equipment such as servers, storage arrays, among other equipment. It can be used for storage, processing and data protection. The majority of data centres operate 24 hours a day, and must provide the user with guarantees in terms of security and performance. Energy consumption is therefore permanent and the level of assistance and maintenance high. Data Centres have an ecological impact that is almost invisible to many users. In this paper a computational fluid dynamics (CFD) model of the airflow and thermal distribution of a real data centre room with 208 racks is proposed. Two case studies are presented and simulated with a high thermal load subjected to the minimum and maximum air flow velocity, respectively. The objective is to assess if the computer room air conditioning unit (CRAC) can cool the racks of the data centre in order to efficiently refrigerate all the hot spots.
机译:数据中心是将计算机设备(例如服务器,存储阵列等)组合在一起的物理空间。它可以用于存储,处理和数据保护。大多数数据中心一天24小时不间断运行,并且必须在安全性和性能方面为用户提供保证。因此,能源消耗是永久性的,援助和维护水平很高。数据中心具有生态影响,许多用户几乎看不到它。本文提出了一个具有208个机架的真实数据中心机房的气流和热分布的计算流体动力学(CFD)模型。给出了两个案例研究,并分别模拟了在高热负荷下分别承受最小和最大空气流速的情况。目的是评估计算机机房空调单元(CRAC)是否可以冷却数据中心的机架,以便有效地冷却所有热点。