首页> 外文会议>Power and Energy Engineering Conference (APPEEC), 2010 >The Study of the Nanosecond pulse method to Detect Winding Deformation of Power Transformer
【24h】

The Study of the Nanosecond pulse method to Detect Winding Deformation of Power Transformer

机译:纳秒脉冲法检测电力变压器绕组变形的研究

获取原文

摘要

Winding deformation is one of the most common faults of power transformers. It may cause partial discharge, even leads to insulation breakdown. Winding deformation also may cause the decreasing of mechanical properties of winding. The study of high sensitive detection method has important significance for detecting minimal change of transformer winding. So authors propose utilizing the nanosecond pulse method to detect winding deformation. Through computer simulations, the parameters of the nanosecond pulse is studied intensively in this paper. By means of analysis, a impulse that has a wave front 5 ns ± 30% and impulse width 50 ns ± 30% has been defined as signal source. To verify the effectiveness of the method, a testing power transformer was detected with the way of the nanosecond pulse. Testing results may reflected winding deformation very well. At the same time, the repeatability is good at the frequency range from 0 to 80 MHz..
机译:绕组变形是电力变压器最常见的故障之一。可能会导致局部放电,甚至导致绝缘击穿。绕组变形还可能导致绕组的机械性能下降。高灵敏度检测方法的研究对检测变压器绕组的最小变化具有重要意义。因此,作者建议利用纳秒脉冲方法来检测绕组变形。通过计算机仿真,对纳秒脉冲的参数进行了深入研究。通过分析,将具有波前5 ns±30%和脉冲宽度50 ns±30%的脉冲定义为信号源。为了验证该方法的有效性,使用纳秒脉冲的方式检测了一个测试电源变压器。测试结果可能很好地反映了绕组变形。同时,在0到80 MHz的频率范围内,重复性很好。