首页> 外文会议>IEEE electrical insulation conference >Incapability of Analog Relay Protection to Detect Generator Stator Winding Ground Failures at Neutral End
【24h】

Incapability of Analog Relay Protection to Detect Generator Stator Winding Ground Failures at Neutral End

机译:模拟继电器保护无法检测中性点发电机定子绕组接地故障

获取原文

摘要

The electromechanical ground protection relay 59GN commonly used in generator protection does not respond to grounds in the bottom ~5% of the stator winding. Recent experience with 4 such failures to large generators suggests that this lack of protection can be a disastrous deficiency. These 4 failures each caused massive damage to the generator, and collectively had a total cost, including repair and loss of generation, close to $500,000,000. This paper will describe those 4 failures, and will discuss newer ground relay systems that monitor and protect the entire stator winding for grounds. The objective of this paper is to encourage owner/operators to add one of the newer relay systems.
机译:发电机保护中常用的机电接地保护继电器59GN不能响应定子绕组底部5%左右的接地。大型发电机发生4次此类故障的最新经验表明,缺乏保护可能是灾难性的缺陷。这4次故障各自对发电机造成了巨大的损害,并且包括维修和发电损失在内的总成本接近5亿美元。本文将描述这4种故障,并讨论监视和保护整个定子绕组接地的新型接地继电器系统。本文的目的是鼓励所有者/运营商添加更新的中继系统之一。