Optimal PMU placement for voltage control

机译:用于电压控制的最佳PMU放置

获取原文

摘要

This paper deals with the optimal phasor measurement unit (PMU) placement problem. In large power system, it is costly to place too many PMUs to achieve real time global observability. In fact, system state can be well estimated by optimally placed limited PMUs' synchronous measurements. Based on the method of voltage control area division, a spectral clustering approach is proposed to divide the network into several zones. Probabilistic Load Flow (PLF) is implemented in the meantime to consider many uncertain scenarios of system operation. In this way, the voltage variation of buses in the same zone can possess close coherency under various operation conditions. Consequently, placing PMUs on the best voltage representative locations, namely central buses of each zone in spectral clustering can improve the voltage observability and controllability while effectively reducing the number of PMUs. Case studies on IEEE 14 bus and 39 bus system are presented.
机译:本文讨论了最佳相量测量单元(PMU)放置问题。在大型电源系统中,放置太多PMU来实现实时全局可观察性是很昂贵的。实际上,通过最佳放置有限的PMU的同步测量可以很好地估计系统状态。基于电压控制区域划分的方法,提出了一种频谱聚类的方法将网络划分为几个区域。同时实施概率潮流(PLF)来考虑系统运行的许多不确定情况。这样,同一区域中母线的电压变化在各种操作条件下都可以具有紧密的相干性。因此,将PMU放置在最佳的电压代表位置上,即频谱聚类中每个区域的中央总线,可以提高电压的可观察性和可控性,同时有效地减少PMU的数量。介绍了有关IEEE 14总线和39总线系统的案例研究。