摘要

The most common causes of malfunctions and types of damage to traction substations power transformers are presented and classified, the influence of the climatic conditions of the region of operation on the reliability of the power transformer insulation is shown. The results of the analysis of the damageability of traction substations' power oil transformers with types of damage to the insulation system on the example of a Russia's railroad. The classification of climatic factors affecting the reliability indicators of isolation is proposed, a model of climatic factors influence on the reliability parameters of the transformer is developed and presented in the form of a generalized integral indicator estimated by the climatic impact score. The classification of climatic factors affects the transformer reliability parameters and allows us to outline and develop a strict technology for monitoring the status of the main parameters that characterize the wear level of the transformers and their readiness to work in the future.
机译:介绍和分类了牵引变电站电力变压器故障和损坏类型的最常见原因,并显示了运行区域的气候条件对电力变压器绝缘可靠性的影响。以俄罗斯铁路为例,分析了牵引变电所的电力油变压器对绝缘系统造成的损坏类型的可损坏性分析结果。提出了影响隔离可靠性指标的气候因素分类,建立了影响变压器可靠性参数的气候因素模型,并以气候影响分数估算的广义积分指标的形式提出。气候因素的分类会影响变压器的可靠性参数,使我们能够概述和开发一种严格的技术来监控主要参数的状态,这些主要参数表征了变压器的磨损程度及其在将来的工作状态。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号