This paper investigates airflow in an office room withrna displacement ventilation system parametricallyrnusing three-dimensional CFD. A numerical study isrnexecuted for a typical office room with a dimensionrnof 6m by 6m by 3m height according to a variety ofrnsupply air velocities, supply air temperatures and heatrnsource conditions. Internal cooling load is given asrn28W/m2 to 111W/m2. In CASE1, a heat source isrninstalled at the center of the room. In CASE2, fourrnheat sources are located separately in the modeledrnroom. The finite volume method and the lowrnReynolds number k- ε turbulence model arernemployed to solve the governing equationsrnnumerically. As a result, the temperature field in thernmodeled room for a displacement ventilation systemrnis concluded according to a variety of the abovernparameters. The stratification profiles in the roomrndepend especially on the supply air velocity. Thisrnmeans VAV systems are applicable to control roomrnair temperature for a displacement ventilation system.rn.
机译:本文研究了使用三维CFD参数设置的办公室排风通风系统中的气流。根据各种供气速度,送风温度和热源条件,对尺寸为6m x 6m x 3m高的典型办公室进行了数值研究。内部冷却负荷为asrn28W / m2至111W / m2。在案例1中,将热源安装在房间的中央。在案例2中,四个热源分别位于模型房间中。运用有限体积法和低雷诺数k-ε湍流模型数值求解控制方程。结果,置换通风系统的模型房间中的温度场根据上述各种参数得出。房间中的分层分布尤其取决于送风速度。这意味着VAV系统适用于控制置换通风系统的室温。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号