首页> 外文会议>Water Environment Federation 75th annual technical exhibition amp; conference (WEFTEC 2002) >Enhancing Copper Removal in Secondary Treatment by Chemical Addition
【24h】

Enhancing Copper Removal in Secondary Treatment by Chemical Addition

机译:通过化学添加提高二级处理中的铜去除率

获取原文
获取原文并翻译 | 示例

摘要

Chemical addition was tested for enhancing copper removal in the University of California,rnDavis (UCD) wastewater treatment plant (WWTP). Wastewater from the headworks andrnoxidation ditch were treated with ferric chloride and two organic precipitants in jar tests. Ferricrnchloride had little effect on residual dissolved copper, while the organic precipitants reduced itrnbelow 10 μg/L. In a full-scale trial, dose of 8 ppm to 13 ppm organic polymer effected a meanrnreduction in dissolved copper concentration of 2 μg/L, sufficient to maintain compliance with thernWWTP’s 13-μg/L water quality-based effluent limit for copper. Full-scale implementationrnrequired no additional solids separation or handling equipment.
机译:在加州大学戴维斯分校(UCD)废水处理厂(WWTP)中测试了添加化学药品对提高铜去除率的作用。在广口瓶试验中,用氯化铁和两种有机沉淀剂处理了渠首和氧化沟的废水。氯化铁对残留的溶解铜几乎没有影响,而有机沉淀剂将其降低到10μg/ L以下。在一项全面试验中,有机聚合物剂量为8 ppm至13 ppm时,平均溶解铜浓度降低了2μg/ L,足以维持污水处理厂基于水质的13μg/ L铜废水极限。全面实施无需额外的固体分离或处理设备。