首页> 中文期刊> 《电力能源(英文)》 >The Method for Measuring the Loop Resistance and the Temperature Rise Calculation of GIS Conductor Pole

The Method for Measuring the Loop Resistance and the Temperature Rise Calculation of GIS Conductor Pole

         

摘要

This paper studies the method for measuring the loop resistance of GIS conductor pole based on the super capacitor producing impulse current up to several thousand amperes. This method overcomes the limitations of conventional diagnostic method. Typical GIS conductor poles are chosen. Based on FEA and lab tests, the effect of different forms of current and contact condition, relationship between the temperature of contact and the loop resistance is researched. In full- scale testing under realistic operating conditions on the new 220 kV GIS using prototype instrumentation a very good sensitivity in an early stage was obtained.