首页> 中文期刊> 《浙江大学学报(英文版)(A辑:应用物理和工程)》 >Experimental study on transient behavior of semi-open two-phase thermosyphon

Experimental study on transient behavior of semi-open two-phase thermosyphon

         

摘要

<正>An experimental system was set up to measure the temperature, pressure, heat transfer rate and mass flow rate in a semi-open two-phase thermosyphon. The behaviors of a semi-open two-phase thermosyphon during startup, shutdown and lack of water were studied to get complete understanding of its thermal characteristics. The variation of wall temperature, heat-exchange condition and pressure fluctuations of semi-open two-phase thermosyphons showed that the startup of SOTPT needs about 60-70 min; the startup speed of SOTPT is determined by the startup speed of the condensation section; the average pressure in the heat pipe is equal to the environmental pressure usually; the shutdown of SOTPT needs about 30~50 min; a semi-open two-phase thermosyphon has good response to lack of water accident.