首页> 美国卫生研究院文献>British Journal of Industrial Medicine >Outbreak of legionnaires disease from a cooling water system in a power station.
【2h】

Outbreak of legionnaires disease from a cooling water system in a power station.

机译:发电厂冷却水系统中爆发军团菌病。

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

In September and October 1981 six cases of pneumonia occurred among men working in a power station under construction. Three were identified as cases of legionella pneumonia and two others had serology suggestive of legionella infection. In a sample of 92 men from the site 10 had low levels of antibodies to legionella; a similar sample of men working on an adjacent site showed none with positive serology. In a case control study it was found that cases of pneumonia were more likely than controls to have worked on a part of the site where four small capacity cooling towers were located. Legionella pneumophila serogroup 1 was isolated from the water systems of these four towers but was not found in samples from any other cooling towers or hot or cold water outlets on the site. It would appear that there was airborne spread of the organism from these cooling water systems which had not received conventional treatment to inhibit corrosion and organic growth. This is the first outbreak of legionnaires' disease to be recorded in an industrial setting in the United Kingdom. No cases of legionella infection have occurred on the site since the introduction of control measures.
机译:1981年9月和1981年10月,在建设中的电站工作的男子中发生了6例肺炎。确定了三例为军团菌肺炎病例,另外两例血清学提示为军团菌感染。在来自该地点的92名男子的样本中,有10名针对军团菌的抗体水平低;在邻近地点工作的男性样本相似,但血清学检查均呈阳性。在病例对照研究中,发现肺炎病例比对照组更可能在四个小容量冷却塔所在的部分场所工作。从这四个塔的水系统中分离出嗜肺军团菌血清群1,但在现场其他任何冷却塔或热水或冷水出口的样品中均未发现军团菌。看来这些冷却水系统中有生物通过空气传播,而没有经过常规处理以抑制腐蚀和有机增长。这是联合王国工业环境中首次记录的军团菌病暴发。自采取控制措施以来,现场未发生军团菌感染病例。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号