首页> 外文期刊>Australian Refrigeration Air Conditioning & Heating >Further progress with mixed refrigerants for power saving
【24h】

Further progress with mixed refrigerants for power saving

机译:混合制冷剂可进一步节省功率

获取原文
获取原文并翻译 | 示例
           

摘要

Tests are reported using the original test rig with a R23/R134a blend. Despite the wide boiling range the unit worked well and gave COP values in the range 3.5 to 4.4. The unit was re-vamped to incorporate new condenser and evaporator designs together with a new patented control system which required a single section evaporator in place of the split unit. The new unit was tested with a CO_2/R134a blend and two ternary blends. Based on these test results air conditioning units are proposed using the R32/R227 mixture which could give COP values of 4 to 5. A review is presented of the challenge of using mixed refrigerants with the proposed novel control system in water chilling, vehicle air conditioning and process applications.
机译:报告是使用带有R23 / R134a混合物的原始测试台进行的。尽管沸程很宽,该装置仍能很好地工作,COP值在3.5至4.4之间。该单元经过重新设计,以结合新的冷凝器和蒸发器设计以及新的专利控制系统,该控制系统需要使用单段蒸发器来代替分流单元。新的单元用CO_2 / R134a共混物和两种三元共混物进行了测试。根据这些测试结果,提出了使用R32 / R227混合物的空调单元,其COP值为4到5。提出了将混合制冷剂与拟议的新型控制系统一起用于水冷,车辆空调的挑战的综述。和处理应用程序。