ANALYZING DATA IS CRUCIAL TO AVERTING CRITICAL FAILURE OF A TRANSFORMER

机译:分析数据对于消除变压器的严重故障至关重要

获取原文
获取原文并翻译 | 示例
           

摘要

The Dresden Unit 2 Main Power Transformer was commissioned in November 2003. During the first three months of operation, the unit experienced some generation of combustible gases. An investigation was performed, including thermography studies of the transformer, and the gassing was correlated to the periods when only half of the coolers were running. No generation of gassing was experienced when all the coolers were running. Further troubleshooting identified that one pump was running backwards.
机译:德累斯顿2号机组主电源变压器于2003年11月投入使用。在运行的前三个月中,该机组产生了一些可燃气体。进行了一项调查,包括对变压器的热成像研究,并且放气与只有一半冷却器运行的时间相关。当所有冷却器运行时,没有发生放气现象。进一步的故障排除发现一个泵正在倒转。