首页> 外文期刊>Electric Power Components and Systems >A Solution to the Dilemma Inrush/Fault in Transformer Differential Relaying Using MRA and Wavelets
【24h】

A Solution to the Dilemma Inrush/Fault in Transformer Differential Relaying Using MRA and Wavelets

机译:基于MRA和小波的变压器差动保护突入/故障的解决方案。

获取原文
获取原文并翻译 | 示例
           

摘要

In this article, multiresolution analysis (MRA) and wavelets are applied to the study of the existence of an internal short circuit in a transformer. An analytical support is given to the proposal of a relaying technique based on the derivation of the existence of specific singularities in the modulus of the space vector as obtained from the three differential signals. The proposal stems from the quite different travel angles of the space vector: maximum 120 degrees for healthy inrush and 360 degrees for fault. The sharp notches in the modulus of the space-vector are then detected using de first detail in MRA.