首页> 外文期刊>Electric power systems research >A PMU-augmented stability power limit assessment for reliable arming of special protection systems
【24h】

A PMU-augmented stability power limit assessment for reliable arming of special protection systems

机译:PMU增强的稳定功率极限评估,可用于特殊保护系统的可靠布防

获取原文
获取原文并翻译 | 示例
           

摘要

This paper studies the application of phasor measurement unit (PMU) data for security-enhanced arming of special protection systems. A PMU-based hybrid method is proposed to assess transient stability limits of a multi-machine system in advance of network contingencies. The method is based on the single machine equivalent (SIME) technique, which combines time-domain algorithms with the direct method of equal-area criterion, to determine stability power limits on major transmission lines. In addition, based on the real-time network condition obtained by synchrophasor measurements, a strategy is proposed to effectively determine whether an arming signal should be issued for the next probable contingency. The effectiveness of the PMU-based automatic arming method is evaluated and discussed through simulation studies conducted in the real-time digital simulator (RTDS) and MATLAB software environment. (C) 2015 Published by Elsevier B.V.
机译:本文研究了相量测量单元(PMU)数据在特殊保护系统的安全性增强武装中的应用。提出了一种基于PMU的混合方法,用于在网络突发事件之前评估多机系统的暂态稳定极限。该方法基于单机等效技术(SIME),该技术将时域算法与等面积标准的直接方法结合在一起,以确定主要传输线上的稳定功率极限。此外,基于通过同步相量测量获得的实时网络状况,提出了一种策略,可以有效地确定是否应为下一个可能的意外事件发出布防信号。通过在实时数字仿真器(RTDS)和MATLAB软件环境中进行的仿真研究,评估并讨论了基于PMU的自动布防方法的有效性。 (C)2015由Elsevier B.V.发布