首页> 外文期刊>Electrical Engineering >Measured electrical constants of 270-mile 154-kv transmission line
【24h】

Measured electrical constants of 270-mile 154-kv transmission line

机译:270英里154 kV输电线路的实测电常数

获取原文
获取原文并翻译 | 示例
           

摘要

C. F. Wagner (Westinghouse Electric and Manufacturing Company, East Pittsburgh, Pa.): The principal value of this paper lies in the comparison between measured and calculated values of the constants of transmission lines. Naturally, therefore, the authors should be explicit in defining the assumptions made in the calculations. Frequently in calculating the characteristics of transmission lines the separation of conductors is taken as the values at the tangent towers. The authors in this instance have gone beyond this assumption and have averaged the separation, taking into consideration the difference in sag of the ground wires and conductors. Further clarification of the method of averaging is desirable. A statement from the authors is also desirable regarding the assumption used in determining the length of conductors. Did they use merely the geographical length of the line, or did they compute the constants on the basis of the actual length of the conductors, taking the sag into consideration? Further clarification is also desirable regarding the basis for using an earth resistivity of 100 ohms per meter cube.
机译:C. F. Wagner(宾夕法尼亚州匹兹堡东威斯汀豪斯电气和制造公司):本文的主要价值在于比较传输线常数的测量值和计算值。因此,自然地,作者应明确定义计算中的假设。通常在计算传输线的特性时,将导体的间距作为切线塔处的值。在这种情况下,作者考虑了接地线和导体垂度的差异,已经超出了这一假设并平均了间隔。希望进一步阐明平均方法。关于确定导体长度所使用的假设,作者的陈述也是可取的。他们是仅使用线路的地理长度,还是在考虑到垂度的情况下根据导体的实际长度计算常数?关于使用每米立方米100欧姆的接地电阻的基础,还需要进一步澄清。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号