The New York Times Headquarters daylighting mockup: Monitored performance of the daylighting control system

机译:纽约时报总部采光模型:监控采光控制系统的性能

获取原文
获取原文并翻译 | 示例
           

摘要

A 9-month monitored field study of the performance of automated roller shades and daylighting controls was conducted in a 401 m~2 unoccupied, furnished daylighting mockup. The mockup mimicked the southwest corner of a new 110 km~2 commercial building in New York, New York, where The New York Times will be the major tenant. This paper focuses on evaluating the performance of two daylighting control systems installed in separate areas of an open plan office with 1.2-m high workstation partitions: (1) Area A had 0-10 V dimmable ballasts with an open-loop proportional control system and an automated shade controlled to reduce window glare and increase daylight, and (2) Area B had digital addressable lighting interface (DALI) ballasts with a closed-loop integral reset control system and an automated shade controlled to block direct sun. Daylighting control system performance and lighting energy use were monitored. The daylighting control systems demonstrated very reliable performance after they were commissioned properly. Work plane illuminance levels were maintained above 90% of the maximum fluorescent illuminance level for 99.9 ± 0.5% and 97.9 ±6.1% of the day on average over the monitored period, respectively, in Areas A and B. Daily lighting energy use savings were significant in both Areas over the equinox-to-equinox period compared to a non-daylit reference case. At 3.35 m from the window, 30% average savings were achieved with a sidelit west-facing condition in Area A while 50-60% were achieved with a bilateral daylit south-facing condition in Area B. At 4.57-9.14 m from the window, 5-10% and 25-40% savings were achieved in Areas A and B, respectively. Average savings for the 7-m deep dimming zone were 20-23% and 52-59% for Areas A and B, respectively, depending on the lighting schedule. The large savings and good reliability can be attributed to the automatic management of the interior shades. The DALI-based system exhibited faulty behavior that remains unexplained, but operational errors are expected to be resolved as DALI products reach full maturity. The building owner received very competitive bids ($30-75 US/DALI ballast) and was able to justify use of the daylighting control system based on operational cost savings and increased amenity. Additional energy savings due to reduced solar and lighting heat gains were not quantified but will add to the total operational cost savings.
机译:在一个401 m〜2空置的带家具采光样机上进行了为期9个月的监测现场研究,研究了自动卷帘和采光控制的性能。该模型模仿了位于纽约纽约的新110 km〜2商业建筑的西南角,《纽约时报》将是其中的主要租户。本文着重评估安装在开放式办公室中具有1.2 m高工作站分区的独立区域中的两个采光控制系统的性能:(1)A区具有0-10 V可调光镇流器,带有开环比例控制系统,以及(2)B区具有数字可寻址照明接口(DALI)镇流器,并带有闭环整体复位控制系统,而自动遮阳帘则受控制以阻止直射阳光。监控日光控制系统的性能和照明能耗。经过适当调试,采光控制系统表现出非常可靠的性能。在监视区域内,在A区和B区,工作平面的照度水平平均每天分别维持在最大荧光照度水平的90%以上,分别为99.9±0.5%和97.9±6.1%。每天节省的照明能源使用量非常可观相较于非日照参考案例,在春分到春分期间这两个区域都存在这种情况。在距窗户3.35 m处,A区侧向朝西的情况下平均节省30%,而在B区双向侧向朝阳的情况下,则达到50-60%。在距窗户4.57-9.14 m处,A区和B区分别节省了5-10%和25-40%。根据照明时间表,A区和B区的7米深调光区平均节省分别为20-23%和52-59%。大量的节省和良好的可靠性可以归因于室内遮阳帘的自动管理。基于DALI的系统表现出无法解释的错误行为,但是随着DALI产品达到完全成熟,预期会解决操作错误。建筑物所有者收到了非常有竞争力的出价($ 30-75 US / DALI镇流器),并且能够基于节省的运营成本和增加的便利性证明使用采光控制系统是合理的。由于减少了太阳能和照明的热量获取而带来的额外能源节省尚未量化,但会增加总的运营成本节省。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号