Transient short-circuit forces are analytically calculated in an arrangement of three parallel and coplanar busbars. Each is enclosed in a tubular, conducting, shell. Results can be used for the design of metal clad connection buses for large generators or similar uses. Shells made of aluminium with 10 mm thickness reduced the forces applied on the phase conductors by a factor of 20 or more as compared with arrangements without shells. Forces applied on a phase conductor and to the corresponding shell have same order of magnitude.
机译:在三个平行且共面的汇流排的布置中,可以分析计算瞬态短路力。每个都封装在管状的导电外壳中。结果可用于大型发电机或类似用途的金属包覆连接母线的设计。与没有外壳的装置相比,由厚度为10 mm的铝制成的外壳将施加在相导体上的力减小了20倍或更多。施加在相线和相应外壳上的力大小相同。