摘要

To study the effect mechanism of air deflectors on dry cooling tower, a three dimensional numerical model was established, with full consideration of the delta structure. The accuracy and credibility of dry cooling tower numerical model were validated. By numerical model, the average air static pressure and the average radial inflow air velocity were computed and analyzed at delta air entry, sector air entry and exit faces. By the air inflow deviation angle theta(d), the effect of air deflectors on the aerodynamic field around tower was analyzed. The water exit temperatures of theta(-1) columns, theta(+2) columns and cooling sectors were also presented to clarify the effect of air deflectors. It was found that the air deflectors improved the aerodynamic field around cooling columns. The reduced air inflow deviation degree at delta entry improved the cooling performance of deteriorated columns. Referring to the radial inflow air velocity u(ra) and the air inflow deviation degree at delta entry, the effect mechanism of air deflectors are clarified under crosswind. (C) 2015 Elsevier Ltd. All rights reserved.
机译:为了研究导流板对干式冷却塔的影响机理,建立了充分考虑三角洲结构的三维数值模型。验证了干式冷却塔数值模型的准确性和可信性。通过数值模型,计算和分析了三角形进气口,扇形进气口和出风面的平均空气静压力和平均径向流入空气速度。通过进风偏角θ(d),分析了导流板对塔周围空气动力场的影响。还介绍了θ(-1)柱,θ(+2)柱和冷却段的出水温度,以阐明导流板的作用。发现导流板改善了冷却塔周围的空气动力场。减少了进入三角形入口处的空气流入偏差度,从而改善了劣化色谱柱的冷却性能。参照径向入风速度u(ra)和进入三角洲时的入风偏离度,明确了侧风作用下导流板的作用机理。 (C)2015 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号