Electricity use characteristics of 10 air-conditioned office buildings in subtropical Hong Kong were investigated. Monthly electricity consumption data were gathered and analysed. The annual electricity use per unit gross floor area ranged from 233 to 368 kWh/m~2, with a mean of 292 kWh/m~2. The ranges of percentage consumption for the four major electricity end-users - namely heating, ventilation and air-conditioning (HVAC), lighting, electrical equipment, and lifts and escalators - were 40.1-50.7%, 22.1-29%, 16.6-32.9% and 2.2-5.3%, respectively. Ten key design variables were identified in the parametric and sensitivity analysis using building energy simulation technique. Analysis of the resulting influence coefficients suggested that indoor design condition (from 22 to 25.5 ℃), electric lighting (a modest 2 W/m~2 reduction in the current lighting code) and chiller COP (from air- to water-cooled) could offer great electricity savings potential, in the order of 14%, 5.2% and 11%, respectively.
机译:研究了香港亚热带地区10座空调办公大楼的用电特征。收集并分析了每月的用电量数据。每单位建筑面积的年用电量在233至368 kWh / m〜2之间,平均为292 kWh / m〜2。四个主要电力最终用户(即供暖,通风和空调(HVAC),照明,电气设备以及升降机和自动扶梯)的百分比消耗范围为40.1-50.7%,22.1-29%,16.6-32.9 %和2.2-5.3%。使用建筑能耗模拟技术在参数和灵敏度分析中确定了十个关键设计变量。对产生的影响系数的分析表明,室内设计条件(从22到25.5℃),电照明(目前的照明规范应适度降低2 W / m〜2)和冷水机组COP(从风冷到水冷)可以具有巨大的节电潜力,分别约为14%,5.2%和11%。