In this paper, the results obtained after monitoring a distribution transformer during an 18 months period are described and discussed. The transformer fed several households, each with a grid connected photovoltaic system, and it was found that the power factor at the transformer attained unusually low levels. This was due to the fact that under some conditions, the systems provided a large portion of the active power demanded by the households, while the grid supplied all the reactive and distortion powers. The operating temperature was used as an indicator of the stress on the transformer. The temperature was at its lowest when the systems were providing the maximum energy available from the solar cells.
机译:在本文中,描述和讨论了在18个月的时间内监视配电变压器后获得的结果。该变压器为数个家庭供电,每个家庭都有一个并网的光伏系统,发现该变压器的功率因数达到了异常低的水平。这是由于以下事实:在某些情况下,系统提供了家庭所需的大部分有功功率,而电网则提供了所有无功和畸变功率。工作温度用作变压器应力的指标。当系统提供太阳能电池提供的最大能量时,温度处于最低温度。