首页> 外文期刊>消防硏究所報告 >Hazard evaluation with closed pressure vessel test
【24h】

Hazard evaluation with closed pressure vessel test

机译:密闭压力容器测试的危害评估

获取原文
获取原文并翻译 | 示例
           

摘要

A closed pressure vessel test (CPVT) was developed in order to measure the temperature and the pressure in the decomposition of sample. It is easier to measure the data with the CPVT than high sensitive calorimeters. The examples of sample were linseed oil bio diesel fuel, refuse derived fuel, coal,alithium coin battery and alithium ion battery. The results of CPVT measurements were compared with the results measured with a high sensitivity calorimeter (C 80) and a spontaneous ignition tester (SIT), and a differential accelerating rate calorimeter (DARC). The data without the heat capacity correction for the sample vessel (phi correction) can be directly obtained with the DARC. The hazard of the oxidation heat and the intensity of decomposition in heating were investigated with the CPVT, the C80, the SIT and the DARC.
机译:为了测量样品分解过程中的温度和压力,开发了密闭压力容器测试(CPVT)。使用CPVT测量数据比使用高灵敏量热仪更容易。样品的例子是亚麻子油生物柴油,垃圾衍生燃料,煤,铝制硬币电池和锂离子电池。将CPVT测量的结果与使用高灵敏度量热仪(C 80),自燃测试仪(SIT)和差加速率量热仪(DARC)测得的结果进行比较。无需使用样品容器进行热容量校正(phi校正)的数据即可直接通过DARC获得。用CPVT,C80,SIT和DARC研究了氧化热的危险和加热中分解的强度。