首页> 外文期刊>Power Engineering Review, IEEE >Field Measurement of Ground Fault Current Distribution and Substation Ground Impedance at LG-2, Qu??bec
【24h】

Field Measurement of Ground Fault Current Distribution and Substation Ground Impedance at LG-2, Qu??bec

机译:魁北克LG-2接地故障电流分布和变电站接地阻抗的现场测量

获取原文
获取原文并翻译 | 示例
           

摘要

Field measurements of ground fault current distribution and substation ground impedance of the LG-2 complex in Quebec, are presented. A high current measuring technique is described in Appendix A. Appendix B illustrates the way current distribution and efficiency were determined. The effectiveness of each grounding element is calculated, showing that the grounding conductors and not the ground grid drain most of the fault current.
机译:介绍了魁北克LG-2电站的接地故障电流分布和变电站接地阻抗的现场测量结果。附录A中描述了一种高电流测量技术。附录B说明了确定电流分布和效率的方式。计算每个接地元件的有效性,表明接地导体而不是接地网会消耗大部分故障电流。