首页> 外文期刊>電気学会論文誌 B:電力·エネルギー部門誌 >Modeling and Experimental Verification of Covered-Conductor for PD Detection in Overhead Distribution Networks: Modeling Covered-Conductor Overhead Distribution Networks for PD Detection
【24h】

Modeling and Experimental Verification of Covered-Conductor for PD Detection in Overhead Distribution Networks: Modeling Covered-Conductor Overhead Distribution Networks for PD Detection

机译:架空配电网中用于局放检测的覆盖导体的建模和实验验证:用于局放检测中的局放覆盖的导体建模

获取原文
获取原文并翻译 | 示例
           

摘要

Partial discharge (PD) measurements are universally accepted as an effective and reliable tool for on-line condition monitoring of high voltage equipments. A relatively new application is conducting on-line high frequency PD measurements to detect falling trees on covered-conductor (CC) overhead distribution lines. In this paper, theoretical model of CC overhead distribution line is presented and the frequency-dependent distributed transmission line (TL) parameters, wave propagation characteristics (attenuation, phase constant, and propagation velocity), and characteristic impedance are calculated. The derived wave propagation characteristics are compared with those obtained from the time domain reflectometry (TDR) measurements to validate the theoretical model of the CC line. An accurate determination of the TL characteristics for CC lines can be used as a design aid to develop PD measuring system for condition monitoring; thus deciding the optimal locations of the sensors in getting reliable PD detection results to detect falling trees on CC overhead distribution lines.
机译:局部放电(PD)测量已被公认为是在线高压设备状态监测的有效且可靠的工具。相对较新的应用程序正在进行在线高频PD测量,以检测覆盖导体(CC)架空配电线上的倒下的树木。本文建立了CC架空配电线路的理论模型,并计算了与频率有关的分布式传输线路(TL)参数,波传播特性(衰减,相位常数和传播速度)以及特性阻抗。将导出的波传播特性与从时域反射法(TDR)测量获得的波传播特性进行比较,以验证CC线的理论模型。准确确定CC线路的TL特性可用作设计辅助,以开发用于状态监测的PD测量系统。从而确定传感器的最佳位置,以获得可靠的PD检测结果,以检测CC架空配电线上的倒下的树木。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号