首页> 外文期刊>電気学会論文誌. B >Temporary Overvoltage Duty of Surge Arresters in Non-effectively Grounded Systems
【24h】

Temporary Overvoltage Duty of Surge Arresters in Non-effectively Grounded Systems

机译:非有效接地系统中电涌放电器的临时过电压义务

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Important characteristics of metal oxide surge arresters depend on the duty of specified temporary overvoltage requirement due to Volt-Ampere characteristics. However, there is hardly any literature where the duty of surge arresters in non-effectively grounded system is investigated. Temporary overvoltage of 1.43pu proposed in effectively grounded systems is too low compared with nearly √3pu in a line-to-ground fault.