A new UPS scheme provides harmonic suppression and input power factor correction

机译:新的UPS方案提供谐波抑制和输入功率因数校正

获取原文
获取原文并翻译 | 示例
           

摘要

A new parallel processing uninterruptible power supply (UPS) configuration is proposed in this paper. It provides active power line conditioning to minimize mains current distortion. This performance is superior to a conventional UPS. A prototype has been implemented and tested to verify its performance. The experimental results show that the input power factor of the proposed UPS is nearly unity, and the total harmonic distortion (THD) of the input current under nonlinear loading is only 3.618% for a mains voltage with THD of 1.633%.
机译:本文提出了一种新的并行处理不间断电源(UPS)配置。它提供有源电源线调节,以最大程度地减小市电电流失真。此性能优于常规UPS。原型已实现并经过测试以验证其性能。实验结果表明,所建议的UPS的输入功率因数几乎为1,对于总谐波失真(THD)为1.633%的市电电压,非线性负载下输入电流的总谐波失真(THD)仅为3.618%。