首页> 外文期刊>International journal of systems,control and communications >Frequency control of an isolated power system considering mutual effects of AGC in presence of energy storage units
【24h】

Frequency control of an isolated power system considering mutual effects of AGC in presence of energy storage units

机译:考虑储能单元存在AGC相互作用的隔离电力系统的频率控制

获取原文
获取原文并翻译 | 示例
           

摘要

Automatic generation control (AGC) of an isolated power system is investigated in this paper. Performance analysis is carried out by considering the mutual coupling effect between load frequency control (LFC) and automatic voltage regulator (AVR) control loops by adding one fixed and one variable energy storage systems (ESS). The insertion of storage devices reduces the frequency oscillations for various load changes and also reduces the mutual effect of LFC and AVR. Simultaneous coordinated tuning of secondary controller and variable storage unit with particle swarm optimisation (PSO) and improved particle swarm optimisation (IPSO) is carried out to provide control strategy for the system. The system is simulated both in presence and absence of secondary controller in which IPSO gives better performance results than PSO. The simulation is carried out in MATLAB/Simulink software.
机译:本文研究了隔离电力系统的自动发电控制(AGC)。通过考虑负载频率控制(LFC)和自动电压调节器(AVR)控制回路之间的相互耦合效应来进行性能分析,方法是添加一个固定和一个可变能量存储系统(ESS)。存储设备的插入减少了各种负载变化的频率振荡,还减少了LFC和AVR的相互影响。通过粒子群优化(PSO)和改进的粒子群优化(IPSO)对辅助控制器和变量存储单元进行同步协调调整,为系统提供控制策略。在存在和不存在辅助控制器的情况下都对系统进行了仿真,其中,IPSO比PSO提供更好的性能结果。仿真是在MATLAB / Simulink软件中进行的。