摘要

In this paper, the lightning performance of the 150 kV transmission line in West Sumatra, Indonesia, is studied in details, showing that the lightning trip-out rate depends on the tower-footing resistance and the length of an arcing horn gap. The observed trip-out rate higher than 20 trip-outs/100 km-year is in good agreement with the results of the simulation by the IEEE FLASH program by using the so-called impulse resistance. The dependency of the trip-out rate on the arm location fairly well agrees with the rate estimated by the IEEE method too.
机译:本文对印度尼西亚西苏门答腊岛150 kV输电线路的雷电性能进行了详细研究,结果表明雷电跳闸率取决于塔架基础电阻和弧形角间隙的长度。观测到的跳闸速率高于每年20个跳闸/ 100 km /年,这与IEEE FLASH程序通过使用所谓的脉冲阻抗进行的仿真结果非常吻合。跳闸速率对手臂位置的依赖性也与IEEE方法估计的速率非常吻合。