An approach for a real-time adaption of the dead time for autoreclosing on high-voltage lines was proposed. The objective was the optimal adaption of the dead time of a currently running single-phase autoreclosing cycle by calculating the secondary arc current based on measurements. The algorithms for optimization were performed for real-time applications. For this purpose, the fault location plus the load currents of the parallel nonfaulty conductors were measured. The measurement and the calculation of the dead time took place during the fault and the dead-time period. In this way, an optimized dead-time setting with regard to the actual fault location and loading conditions were achieved. This approach results in an online determination of the minimum necessary dead time of a successful reclosing under consideration of the fault location and prevailing loading conditions. Analytical calculations and numerical examples as well as high-voltage field tests verified the results.
机译:提出了一种实时调整停滞时间以自动重合高压线路的方法。目的是通过基于测量值计算次级电弧电流,以最佳方式适应当前运行的单相自动重合闸周期的停滞时间。优化算法是针对实时应用程序执行的。为此,测量了故障位置以及并联无故障导体的负载电流。死区时间的测量和计算是在故障和死区时间段内进行的。通过这种方式,可以实现针对实际故障位置和负载条件的优化死区时间设置。这种方法可以在线确定成功重合闸的最小必要停滞时间,同时考虑故障位置和主要载荷条件。分析计算和数值示例以及高压现场测试验证了结果。