首页> 外文期刊>IEEE Transactions on Power Delivery >Observation and analysis of lightning surges at substations connected with UHV designed transmission lines
【24h】

Observation and analysis of lightning surges at substations connected with UHV designed transmission lines

机译:与特高压输电线路相连的变电站雷电浪涌的观察与分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

On UHV-class transmission lines with sections of 500 kV class insulation, lightning observations have been made to study the generation and the propagation of overvoltage into substations. Voltages and currents were recorded at substations and at junction-tower footings during three flashovers on the UHV system. These observations were then matched to EMTP calculations by adjusting the average soil resistivity and the average conductor height in the propagation model. It is also found that the attenuation due to corona of voltages was small because it is expected to be minimal for 8-conductor bundles.
机译:在绝缘等级为500 kV级的特高压输电线路上,进行了雷电观测,以研究过电压在变电站中的产生和传播。在特高压系统的三次闪络期间,在变电站和交叉路口塔基处记录了电压和电流。然后,通过调整传播模型中的平均土壤电阻率和平均导体高度,将这些观测值与EMTP计算相匹配。还发现由于电压电晕引起的衰减很小,因为预期对于8导体束来说衰减最小。