首页> 外文期刊>IEEE Transactions on Power Delivery >Inductive interference caused to telecommunication cables by nearbyAC electric traction lines. Measurements and FEM calculations
【24h】

Inductive interference caused to telecommunication cables by nearbyAC electric traction lines. Measurements and FEM calculations

机译:附近的交流电力牵引线对电信电缆造成的感应干扰。测量和有限元计算

获取原文
获取原文并翻译 | 示例
           

摘要

The paper investigates the inductive interference caused by ACnelectric traction lines to nearby buried telecommunication cables.nMeasurements according to the directives of the InternationalnTelecommunication Union (ITU) and calculations using the finite elementnmethod (FEM) are presented for a real system. This system consists of annAC electric traction line of the Greek Railways Organization and anburied cable of the Greek Telecommunications Organization. Finally, annanalysis concerning the most important operational parameters inndetermining electric traction line influence is presented. Suchnparameters are the separation distance between the electric tractionnline and the buried telecommunication cable, the earth resistivity asnwell as the number and the material of the mitigation wires
机译:本文研究了交流电牵引线对附近的埋入式通信电缆造成的感应干扰。n提出了根据国际电信联盟(ITU)指令进行的测量以及使用有限元方法(FEM)进行的实际系统计算。该系统由希腊铁路组织的annAC电力牵引线和希腊电信组织的埋入电缆组成。最后,对影响电力牵引线影响的最重要的运行参数进行了分析。这些参数是电力牵引线与埋入的电信电缆之间的距离,接地电阻率以及缓解导线的数量和材料