摘要

Many utilities still have paper-insulated pipe type cables innservice. In the near future they may have to replace some of thesensystems due to local increases in electric power demand or aged cableninsulation. In many cases the steel pipes are well protected againstncorrosion and thus suitable for further use. For retrofitting in suchninstallations, XLPE-insulated cables offer several advantages. Feltenn& Guilleaume Energietechnik AG has developed a new three-corenXLPE-insulated 64/110 kV cable with reduced insulation thickness (10nmm), that can be pulled into a pipe. In co-operation with VEW ENERGIEnAG, the cable performance is being investigated in a field test, thatnstarted in October 1996. This long-term loading cycle test will last fornthree years. The test voltage, applied between conductor and earth,namounts to 127 kV. The temperature is measured with the help of annoptical-fiber measurement system. This device is computer controlled andnworks as a remote monitoring system
机译:许多公用事业公司仍然使用纸绝缘管式电缆。在不久的将来,由于当地电力需求的增加或电缆绝缘层的老化,他们可能不得不更换一些传感器系统。在许多情况下,钢管受到很好的防腐保护,因此适合进一步使用。为了在这种安装中进行改装,XLPE绝缘电缆具有许多优点。 Feltenn&Guilleaume Energietechnik AG开发了一种新的三芯XLPE绝缘64/110 kV电缆,具有减小的绝缘厚度(10nmm),可以拉入管道。与VEW ENERGIEnAG的合作,正在从1996年10月开始的现场测试中研究电缆的性能。这种长期的负载循环测试将持续三年。在导体和大地之间施加的测试电压最高为127 kV。温度是通过非常规纤维测量系统来测量的。此设备是计算机控制的,并且可以作为远程监控系统

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号