Following are hierarchy of control measures and application examples for arc flash hazards. 1) Elimination: System and facility designs that eliminate risk and exposure to arc hazards. 2) Substitution of less hazardous system or equipment: Current-limiting fuses and circuit breakers to limit magnitude of arc flash energy; high resistance grounding to limit frequency and magnitude of high energy arcs in 480 V power systems. 3) Engineering controls: IP20-compliant shrouding on terminal blocks and devices to minimize possibility of tool or metallic object initiating an arc flash event; remote switching to place personnel outside arc flash boundary.
机译:以下是弧光危害的控制措施层次和应用示例。 1)消除:系统和设施设计消除了风险并避免了电弧危害。 2)替代危害较小的系统或设备:限流熔断器和断路器,以限制电弧闪光能量的大小;高电阻接地可限制480 V电力系统中高能电弧的频率和大小。 3)工程控制:在端子排和设备上采用IP20防护罩,以最大程度地减少工具或金属物体引发电弧闪光事件的可能性;远程切换,将人员放置在弧闪范围之外。