This paper presents the design of energy generation based on the national grid, solar photovoltaic (PV), and diesel-based supply systems for a commercial building in Obanikoro, Lagos with a total demand and peak load of 56,000 kWh/yr and 13.5 kW, respectively. The grid is simulated based on the average daily supply of 6 hours being experienced in the study location, indicating that the building is not served for an average of 18 hours/day. The paper considers three design configurations: grid, grid +PV, and grid + PV + generator systems in HOMER Microgrid tool and their performances are compared in terms of the annual generation, load not served, and the emissions. A load demand of ~14,000 kWh/yr meaning that 75 % of total demand is not met. A 35.2kWPV was added to the grid, with both supplying 49,687 and 13,826 kWh/yr, respectively. However, a 6.98% of the load is not served. A 15 kW generator is then added to form the grid + PV+ diesel generator configuration, and the participating energy sources supply 15,818, 49,723 and 4,834 kWh/yr, respectively. This configuration is able to meet the demand without any deficit. The CO2, CO, unburned hydrocarbons, particulate matter and SO2 and nitrogen oxides emissions for the three configurations are 8.824, 0, 0, 0, 0.0383 and 0.0187 tonnes/yr; 8.192, 0, 0, 0, 0.0355 and 0.0174 tonnes/yr, and 11.833, 0.0259, 0.00113, 0.000157, 0.0435 and 0.0407 tonnes/yr, respectively. The study can help to mitigate the energy shortage in commercial buildings.
机译:介绍了设计的能量一代基于国家电网、太阳能光伏(PV)和diesel-based供应系统在Obanikoro商业建筑,拉各斯总需求与56000年的峰值负载分别千瓦时/年和13.5千瓦。模拟基于平均每日供应6小时被经验丰富的位置的研究中,表明建设不是一个平均18个小时/天。三个设计配置:网格,网格+ PV,网格+光伏+发电机系统在荷马微型智能电网"工具和比较他们的表演一年一度的一代、负载不服务,的排放。这意味着不满足总需求的75%。35.2 kwpv添加到网格,两者兼而有之分别提供49687和13826千瓦时/年。然而,6.98%的负载不是。千瓦发电机然后添加到网格+光伏+形式柴油发电机配置,和15818年参与能源供应,分别为49723和4834千瓦时/年。配置能够满足需求任何赤字。颗粒物和二氧化硫和氮氧化物排放三个配置是8.824,0.0259, 0.00113, 0.000157, 0.0435和0.0407吨/年,分别。缓解能源短缺的商业建筑。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号