首页> 外文期刊>Electric Power Systems Research >Non-unit traveling wave protection for flexible HVDC lines based on the ratio of the waveform fitting residual
【24h】

Non-unit traveling wave protection for flexible HVDC lines based on the ratio of the waveform fitting residual

机译:Non-unit traveling wave protection for flexible HVDC lines based on the ratio of the waveform fitting residual

获取原文
获取原文并翻译 | 示例
           

摘要

To solve the problems of sensitivity and rapidity of flexible DC line protection from the perspective of the time domain waveform difference of the fault traveling wave (TW), a mathematical analysis of the waveform char-acteristics of the fault-generated TW of the flexible HVDC line is developed in this paper. Moreover, the dif-ference in the time domain expression between the voltage TW is obtained under internal and external faults. To extract the features of the voltage TW waveform, the Levenberg-Marquardt method is used for data fitting according to two fitting functions corresponding to the internal and external faults. Then, a non-unit travelling wave protection scheme based on the ratio of these two fitting residuals is proposed. Finally, extensive simu-lations based on PSCAD/EMTDC show that the scheme can reliably identify all the faults of the DC line within 1 ms and has a high sensitivity and strong robustness under noise interference and different operation modes.

著录项

获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有