首页> 外文期刊>biotechnology progress >Characteristics and Performance of an Autotuning Proportional Integral Derivative Controller for Dissolved Oxygen Concentration
【24h】

Characteristics and Performance of an Autotuning Proportional Integral Derivative Controller for Dissolved Oxygen Concentration

机译:Characteristics and Performance of an Autotuning Proportional Integral Derivative Controller for Dissolved Oxygen Concentration

获取原文
           

摘要

AbstractThe characteristics and performance of an autotuning proportional integral derivative (PID) controller developed by us have been investigated. The parameters for this controller, proportional gain,K, the integral time constant,Ti, and the derivative time constant,Td, are on‐line‐tuned by using heuristic rules, requiring no αpriorituning. The controller showed a stable and robust performance, even when onlyKwas on‐line‐tuned. However, the dynamic (or time delay) of the membrane‐type dissolved oxygen (DO) probe caused oscillations in the DO concentration unless it was properly compensated. This required a prediction method. When all three controller parameters were on‐line‐adjusted, the DO probe dynamic could be effectively overcome with no separate p